Abstract
The effect of the filling ratio (25% ≤ FR ≤ 98%) on the heat transfer performance of a novel two-phase closed thermosyphon (TPCT) combined with a superhydrophilic (SHi) evaporator and slippery lubricant-infused porous surface (SLIPS) condenser (TPCT-SHiSL) is systematically investigated in the present study. On the evaporator side, experimental results show that a different evaporation mechanism takes place dependent on the filling ratio, which has a strong impact on the overall heat transfer performance. Film evaporation plays a dominant role at the filling ratio of 25% and at the filling ratios of 40% and 70% at low heat flux. Nonetheless, film evaporation is gradually reduced and pool boiling becomes important at the filling ratios of 40% and 70% for moderate and high heat fluxes. Finally, pool boiling plays a dominant role for the TPCT-SHiSL at the filling ratio of 98%. In the case of the condenser, the condensation heat transfer of the SLIPS is reduced with increasing filling ratio. Balancing between the thermal resistance and heat transfer capacity, the TPCT-SHiSL at the filling ratio of 40% shows the best heat transfer performance.
| Original language | English |
|---|---|
| Pages (from-to) | 725-736 |
| Number of pages | 12 |
| Journal | International journal of heat and mass transfer |
| Volume | 115 |
| Early online date | 27 Jul 2017 |
| DOIs | |
| Publication status | Published - 1 Dec 2017 |
Keywords / Materials (for Non-textual outputs)
- Boiling heat transfer
- Dropwise condensation
- Film evaporation
- SLIPS
- Superhydrophilic evaporator